Dynamic Processes and Active Power Control of Hydropower Plants
Uppsala universitet, Teknisk-naturvetenskapliga vetenskapsområdet, Tekniska sektionen, Institutionen för teknikvetenskaper, Elektricitetslära. (Hydropower)ORCID-id: 0000-0003-1638-0792
2015 (engelsk)Licentiatavhandling, med artikler (Annet vitenskapelig)
Abstract [en]

Hydro-electricity plays an important role in the safe, stable and efficient operation of electric power systems. Frequency stability of power systems refers to the ability to maintain steady frequency following a severe system upset resulting in a significant imbalance between generation and load. In order to suppress power grid frequency fluctuations, generating units change their power output automatically according to the change of grid frequency, to make the active power balanced again. This is the primary frequency control (PFC). PFC of electrical power grids is commonly performed by units in hydropower plants (HPPs), because of the great rapidity and amplitude of their power regulation.

A hydropower generation system is a complex nonlinear power system including hydraulic, mechanical, electrical and magnetic subsystems. Nowadays, the size of HPPs and the structure complexity of systems have been increasing, especially in China. The proportion of electricity generated by intermittent renewable energy sources have also been growing. Therefore, the performance of HPPs in terms of frequency control is more and more important. The research on control strategies and dynamic processes of HPPs is of great importance. The frequency stability of hydropower units is a critical factor of power system security and power quality. The power response time for evaluating the frequency regulation quality, is also a key indicator.

In recent years, there is a tendency that the new turbines experience fatigue to a greater extent than what seem to be the case for new runners decades ago, due to more regulation movements caused by increasingly more integration of intermittent renewable energy sources. In some countries, as in Sweden, PFC is a service that the transmission system operator buys from the power producers. In other countries, as in Norway and China, there is also an obligation for the producers to deliver this service, free of charge. However, there are costs related to this, e.g. due to design constraints and auxiliary equipment when purchasing a new unit or system, and due to wear and tear which affects the expected life time and maintenance intervals. Hence the specific research on wear and tear of hydro units due to PFC is exceedingly necessary. 

sted, utgiver, år, opplag, sider
Uppsala: Institutionen för teknikvetenskaper; Elektricitetslära , 2015. , s. 53
HSV kategori
Forskningsprogram
Teknisk fysik med inriktning mot elektricitetslära
Identifikatorer
URN: urn:nbn:se:uu:diva-262768OAI: oai:DiVA.org:uu-262768DiVA, id: diva2:855346
Presentation
2015-10-19, Polhemsalen, Ångströmlaboratoriet (Ång/10134), Lägerhyddsvägen 1, Uppsala, 10:15 (engelsk)
Opponent
Veileder
Tilgjengelig fra: 2015-10-14 Laget: 2015-09-20 Sist oppdatert: 2015-10-14bibliografisk kontrollert
Delarbeid
1. Response time for primary frequency control of hydroelectric generating unit
Åpne denne publikasjonen i ny fane eller vindu >>Response time for primary frequency control of hydroelectric generating unit
2016 (engelsk)Inngår i: International Journal of Electrical Power & Energy Systems, ISSN 0142-0615, E-ISSN 1879-3517, Vol. 74, s. 16-24Artikkel i tidsskrift (Fagfellevurdert) Published
Abstract [en]

For evaluating the power quality in primary frequency control for hydroelectric generating units, the power response time is an indicator which is of main concern to the power grid. The aim of this paper is to build a suitable model for conducting reliable simulation and to investigate the general rules for controlling the power response time. Two huge hydropower plants with surge tank from China and Sweden are applied in the simulation of a step test of primary frequency control, and the result is validated with data from full scale measurements. From the analytical aspect, this paper deduces a time domain solution for guide vane opening response and a response time formula, of which the main variables are governor parameters. Then the factors which cause the time difference, between the power response time and the analytical response time of opening, are investigated from aspects of both regulation and water way system. It is demonstrated that the formula can help to predict the power response and supply a flexible guidance of parameter tuning, especially for a hydropower plant without surge tank.

HSV kategori
Identifikatorer
urn:nbn:se:uu:diva-259529 (URN)10.1016/j.ijepes.2015.07.003 (DOI)000362309100003 ()
Forskningsfinansiär
StandUp
Tilgjengelig fra: 2015-08-07 Laget: 2015-08-07 Sist oppdatert: 2017-12-04bibliografisk kontrollert
2. Frequency Stability of Isolated Hydropower Plant with Surge Tank Under Different Turbine Control Modes
Åpne denne publikasjonen i ny fane eller vindu >>Frequency Stability of Isolated Hydropower Plant with Surge Tank Under Different Turbine Control Modes
2015 (engelsk)Inngår i: Electric power components and systems, ISSN 1532-5008, E-ISSN 1532-5016, Vol. 43, nr 15, s. 1707-1716Artikkel i tidsskrift (Fagfellevurdert) Published
Abstract [en]

Currently, the Thoma criterion is often violated to diminish the cross-section of the surge tank; therefore, the surge fluctuation is aggravated and the frequency stability becomes more deteriorative. The focus of this article is on stabilizing the low-frequency oscillation of an isolated hydropower plant caused by surge fluctuation. From a new perspective of hydropower plant operation mode, frequency stability under power control is investigated and compared with frequency control by adopting the Hurwitz criterion and numerical simulation. In a theoretical derivation, the governor equations of frequency control and power control are introduced to the mathematical model. For numerical simulation, a governor model with a control mode switch-over function is built. The frequency oscillations under frequency control, power control, and control mode switch-over are simulated and investigated, respectively, with different governor parameters and operation cases. The result shows that the power control has a better performance on frequency stability at the expense of rapidity compared with the frequency control. Other recommendations regarding worst operation cases and choice of control modes are also developed.

HSV kategori
Identifikatorer
urn:nbn:se:uu:diva-260774 (URN)10.1080/15325008.2015.1049722 (DOI)000359869100003 ()
Tilgjengelig fra: 2015-08-24 Laget: 2015-08-24 Sist oppdatert: 2017-12-04bibliografisk kontrollert
3. A Mathematical Model and Its Application for Hydro Power Units under Different Operating Conditions
Åpne denne publikasjonen i ny fane eller vindu >>A Mathematical Model and Its Application for Hydro Power Units under Different Operating Conditions
Vise andre…
2015 (engelsk)Inngår i: Energies, E-ISSN 1996-1073, Vol. 8, nr 9, s. 10260-10275Artikkel i tidsskrift (Fagfellevurdert) Published
Abstract [en]

This paper presents a mathematical model of hydro power units, especially the governor system model for different operating conditions, based on the basic version of the software TOPSYS. The mathematical model consists of eight turbine equations, one generator equation, and one governor equation, which are solved for ten unknown variables. The generator and governor equations, which are different under various operating conditions, are presented and discussed in detail. All the essential non-linear factors in the governor system (dead-zone, saturation, rate limiting, and backlash) are also considered. Case studies are conducted based on one Swedish hydro power plant (HPP) and three Chinese plants. The simulation and on-site measurements are compared for start-up, no-load operation, normal operation, and load rejection in different control modes (frequency, opening, and power feedback). The main error in each simulation is also discussed in detail. As a result, the model application is proved trustworthy for simulating different physical quantities of the unit (e.g., guide vane opening, active power, rotation speed, and pressures at volute and draft tube). The model has already been applied effectively in consultant analyses and scientific studies.

HSV kategori
Identifikatorer
urn:nbn:se:uu:diva-262746 (URN)10.3390/en80910260 (DOI)000362553000064 ()
Merknad

Correction in: Energies 9(6) Article number: 477 DOI: 10.3390/en9060477

Tilgjengelig fra: 2015-09-18 Laget: 2015-09-18 Sist oppdatert: 2023-08-28bibliografisk kontrollert
4. Wear and tear on hydro power turbines: influence from primary frequency control
Åpne denne publikasjonen i ny fane eller vindu >>Wear and tear on hydro power turbines: influence from primary frequency control
Vise andre…
2016 (engelsk)Inngår i: Renewable energy, ISSN 0960-1481, E-ISSN 1879-0682, Vol. 87, s. 88-95Artikkel i tidsskrift (Fagfellevurdert) Published
Abstract [en]

Nowadays the importance and need of primary frequency control of hydro power units are significantly increasing, because of the greater proportion of intermittent renewable energy sources and more complex structure of power systems. It brings a problem of increasing wear and tear of turbines. This paper studies this problem by applying numerical simulation and concise theoretical derivation, from the point view of regulation and control. Governor models under opening and power feedback mode are built and validated by measurement data. The core index, guide vane movement, is analyzed based on ideal sinusoidal frequency input and real frequency records. The results show the influences on wear and tear of different factors, e.g. governor parameters, power feedback mode and nonlinear governor factors.

HSV kategori
Identifikatorer
urn:nbn:se:uu:diva-262747 (URN)10.1016/j.renene.2015.10.009 (DOI)000367759500008 ()
Tilgjengelig fra: 2015-09-18 Laget: 2015-09-18 Sist oppdatert: 2025-02-17bibliografisk kontrollert
5. Wear reduction for hydro power turbines considering frequency quality of power systems: a study on controller filters
Åpne denne publikasjonen i ny fane eller vindu >>Wear reduction for hydro power turbines considering frequency quality of power systems: a study on controller filters
Vise andre…
2017 (engelsk)Inngår i: IEEE Transactions on Power Systems, ISSN 0885-8950, E-ISSN 1558-0679, Vol. 32, nr 2, s. 1191-1201Artikkel i tidsskrift (Fagfellevurdert) Published
Abstract [en]

Nowadays, the wear and tear of hydropower turbines is increasing, due to more regulation movements caused by the increasing integration of intermittent renewable energy sources. In this paper, a controller filter is proposed as a solution to the tradeoff between reducing the wear of turbines and maintaining the regulation performance and thereby the frequency quality of the power systems. The widely used dead zone is compared with a floating dead zone and a linear filter, by time-domain simulation and frequency-domain analysis. Simulink models are built and compared with onsite measurement. Then, the time-domain simulation is used to investigate the guide vane movement, the load disturbance and the power system frequency, based on a one-day grid frequency datameasured in this study. In the theoretical analysis, the describing functions method and the Nyquist criterion are adopted to examine the stability of the system with different filters. The results show that the floating dead zone, especially the one after the controller, has a better performance than the dead zone on both the wear reduction and frequency quality. The linear filter has a relatively weak impact on both guide vane movements and the frequency quality. Other related conclusion and understandings are also obtained.

HSV kategori
Identifikatorer
urn:nbn:se:uu:diva-262748 (URN)10.1109/TPWRS.2016.2590504 (DOI)000395865900033 ()
Tilgjengelig fra: 2015-09-18 Laget: 2015-09-18 Sist oppdatert: 2025-02-17bibliografisk kontrollert

Open Access i DiVA

fulltext(1004 kB)4153 nedlastinger
Filinformasjon
Fil FULLTEXT01.pdfFilstørrelse 1004 kBChecksum SHA-512
e185f8c5572e7bf4225feeee818f583130932a38d870ee0b3c7b226956111de7c74878cc6907d47754c49e2424f7add238b86315f23aad6d9a73be393607925b
Type fulltextMimetype application/pdf

Person

Yang, Weijia

Søk i DiVA

Av forfatter/redaktør
Yang, Weijia
Av organisasjonen

Søk utenfor DiVA

GoogleGoogle Scholar
Totalt: 4176 nedlastinger
Antall nedlastinger er summen av alle nedlastinger av alle fulltekster. Det kan for eksempel være tidligere versjoner som er ikke lenger tilgjengelige

urn-nbn

Altmetric

urn-nbn
Totalt: 3124 treff
RefereraExporteraLink to record
Permanent link

Direct link
Referera
Referensformat
  • apa
  • ieee
  • modern-language-association
  • vancouver
  • Annet format
Fler format
Språk
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Annet språk
Fler språk
Utmatningsformat
  • html
  • text
  • asciidoc
  • rtf