Study on responses of SPDs against the transient voltages generated by CG flashesShow others and affiliations
2018 (English)Conference paper, Published paper (Refereed)
Abstract [en]
This study presents the behavior of surge protecting devices (SPDs) against transient over voltages generated by cloud to ground (CG) flashes. Analysis revealed that lightning generated transient over voltages have a potential to impart detrimental effects on the SPDs. Moreover, it was concluded that comparisons between IEC laboratory impulse and the real transient voltages are remote due to factors such as peculiar time domain voltage profiles, random polarities, multiple surges with very narrow inter pulse durations in the order of microseconds. Further, observed that SPDs would not always retain within the limits specified by the manufactures under all circumstances.
Place, publisher, year, edition, pages
IEEE, 2018.
National Category
Meteorology and Atmospheric Sciences
Identifiers
URN: urn:nbn:se:uu:diva-368799ISI: 000518213400175ISBN: 978-1-5386-6635-7 (electronic)OAI: oai:DiVA.org:uu-368799DiVA, id: diva2:1268966
Conference
34th International Conference on Lightning Protection,Rzeszow, Poland, 2-7 Sept, 2018
2018-12-072018-12-072025-02-07Bibliographically approved